EVX12260

 

Cells Per Unit 6
Voltage Per
Unit
12 V
Capacity 26 Ah @ 20hr-rate to 1.75V per cell @ 25°C (77°F)
Weight Approx. 8.65 kg. (19.06 lbs..)
Maximum Discharge Current 350A (5 sec)
Internal Resistance Approx. Approx. 9.6 mΩ
Operating Temperature Range Discharge:-15℃~50℃(5°F~122°F)
Charge:-15℃~40℃(5°F~104°F)
Storage:-15℃~40℃(5°F~104°F)
Nominal Operating Temperature Range 25°C ± 3°C (77°F ± 5°F)
Float Charging Voltage 13.5 to 13.8 VDC/unit Average at 25°C (77°F)
Recommended Maximum Charging current limit 7.8A
Equalization and Cycle Service 14.4 to 15.0 VDC/unit Average at 25°C (77°F)
Self Discharge It should be more than 75% of the capacity that before storage after stocked for 6 months at ambient temp. 25℃
Terminal B1/B3/B3B-L terminal or recessed type to accept M5 bolt
Container Material ABS(UL94-HB)