EVX12650

 

Cells Per Unit 6
Voltage Per
Unit
12 V
Capacity 65 Ah @ 20 Hr-Rate to 1.75V Per Cell @ 25℃(77℉)
Weight Approx. 22.2kg. (48.89 lbs.)
Maximum Discharge Current 500A (5 sec)
Internal Resistance Approx. Approx. 4.6 mΩ
Operating Temperature Range Discharge:-15℃~50℃(5°F~122°F)
Charge:-15℃~40℃(5°F~104°F)
Storage:-15℃~40℃(5°F~104°F)
Nominal Operating Temperature Range 25°C ± 3°C (77°F ± 5°F
Float Charging Voltage 13.5 to 13.8 VDC/unit Average at 25°C (77°F)
Recommended Maximum Charging current limit 19.5A
Equalization and Cycle Service 14.4 to 15.0 VDC/unit Average at 25°C (77°F)
Self Discharge It should be more than 75% of the capacity that before storage after stocked for 6 months at ambient temp. 25℃
Terminal B4-L terminal or Recessed Type to accept M6 nut & bolt
Container Material Polypropylene(UL 94-HB)