GP672

 

Cells Per Unit 3
Voltage Per
Unit
6 V
Capacity 7.2 Ah @ 20hr-rate to 1.75V per cell @ 25°C (77°F)
Weight (kg) Approx. 1.22 kg. (2.68 lbs.)
Maximum Discharge current (A) 100A/130A (sec..)
Internal Resistance Approx. Approx. 12.3 mΩ
Operating Temperature Range Discharge:-15℃~50℃(5°F~122°F)
Charge:-15℃~40℃(5°F~104°F)
Storage:-15℃~40℃(5°F~104°F)
Nominal Operating Temperature Range 25°C ± 3°C (77°F ± 5°F)
Float charging voltage 6.75 to 6.9 VDC/unit Average at 25℃ (77°F )
Recommended Maximum Charging current limit 2.16A
Equalization and Cycle Service 7.2 to 7.5 VDC/unit Average at 25℃ (77°F )
Self Discharge It should be more than 75% of the capacity that before storage after stocked for 6 months at ambient temp. 25℃
Terminal F1/F2-Faston Tab187/250
Container Material ABS(UL94-HB) & Flammability resistance of(UL94-V0) can be available upon request.