HRL1234W

 

Cells Per Unit 6
Voltage Per
Unit
12 V
Capacity 34W @ 15 Minute-Rate to 1.67V Per Cell @ 25°C(77°F)
Weight Approx. 2.7 kg(5.95 lbs)
Maximum Discharge Current 130A (5 Sec)
Internal Resistance Approx. Approx. 17 mΩ
Operating Temperature Range Discharge:-15℃~50℃(5°F~122°F)
Charge:-15℃~40℃(5°F~104°F)
Storage:-15℃~40℃(5°F~104°F)
Nominal Operating Temperature Range 25°C±3°C(77°F±5°F)
Float Charging Voltage 13.5 to 13.8 VDC/Unit Average at 25°C(77°F)
Recommended Maximum Charging Current Limit 3.4A
Equalization and Cycle Service 14.4 to 15.0 VDC/Unit Average at 25°C(77°F)
Self Discharge It should be more than 75% of the capacity that before storage after stocked for 6 months at ambient temp. 25℃
Terminal F2-Faston Tab 250
Container Material ABS(UL94-HB) & Flammability resistance of(UL94-V0) can be available upon request.