TPL121250A
| Cells Per Unit | 6 |
| Voltage Per Unit |
12 V |
| Capacity | 125Ah @ 8hr-rate to 1.75V per cell @ 25°C (77°F) |
| Weight | Approx. 44.7 Kg (98.52 lbs) |
| Maximum Discharge current | 800A (5sec) |
| Internal Resistance | Approx. 4.50 mΩ |
| Operating Temperature Range | Discharge:-15℃~50℃ (5°F~122°F) Charge:-15℃~40℃ (5°F~104°F) Storage:-15℃~40℃ (5°F~104°F) |
| Nominal Operating Temperature Range | 25℃±3℃ (77°F±5°F) |
| Float charging voltage | 13.5 ~ 13.8 VDC/Unit Average at 25℃ (77℉) |
| Recommended Maximum Charging current limit | 37.5A |
| Self Discharge | Less than 10% after 90 days, can be stored up to 6 months at 25℃ (77℉) |
| Terminal | I2 thread lead alloy terminal to accept M6 bolt |
| Container Material | Flame Retardant ABS (UL 94-V0) |